BOSER Industrial Partner

DTB-R232 - Boser DTB-R232 Power Supply - Boser DTB-R232 230W Redundant Power...

larger image

Request Quote
For Price
Part Number:
DTB-R232
Model Number:
DTB-R232
Make:
BOSER
Lead Time:
Available
Qty In Stock:
Available

Boser DTB-R232 Power Supply - Boser DTB-R232 230W Redundant Power Supply Simple Type: Power Supply

Boser DTB-R232 230W redundant power supply.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • None Available

Specifications

    General
  • Altitude: 10,000 feet
  • Connectors: AC: One AC input socket
  • DC: 01 DIN 41612 C96
  • Dimensions: 14.0 x 15.0 x 8.62 cm +/-5mm toterance
  • Efficiency: > 70% at rated load
  • EMI: FCC class B / EN55022 B
  • EMS: Level 3 of IEC-801, 802, 803, 804
  • Hold Up Time: > 16ms at 115VAC input and rated load measured from the last AC line charging pulse to the point when +5V drops to +4.75V
  • Humidity: 5~95%; non-condensing at 40°C (operating)
  • Input Current: Does not exceed 30A at 115VAC input or 60A AC input, at cold start 25°C
  • Input Frequency: 47~63Hz
  • Input Voltage: 90~132VAC or 180~260VAC
  • Line Regulation: < +/-1% for each output at rated load and +/-10% of 115VAC or 230VAC input voltage change
  • Load Range: When all outputs are in 60% rated load condition, the +5V output is set between 4.98~5.02V while all other outputs are within the specified voltage accuracy range
  • Load regulation: The output voltage load regulaton is less than the value on the table when subjected to +/-40% change on each output load from 60% rated load, and while all other outputs are at 60% rated load
  • MTBF: 235,743 hrs.
  • Output Power: The total DC continuous power is within 230W at < 30°C ambient temperature
  • Power Good Signal: When turned on, the signal goes high 100~500ms after all output DC voltages are within regulaton limits
  • Power Redundancy: This power supply has power redundant capability
  • Protection: Built-in over ovltage protection circuit shuts down the outputs to prevent damage. Trip point of crowbar circuit is between 5.7~7V; latch off mode against short circuit or over load conditions AC lone NO/OFF cycle recovers unit from fault conditions
  • Ripple And Noise: Peak to peak ripple and noise for +5V, outputs is < 50mV, and < 100mV for +12V, -12V, -5V outputs at rated load, 115/230 VAC
  • Safety: UL 1950 / CSA 22.2 No.234 / VDE EN60950
  • Temperature: 0~+40°C (operating); -40~+75°C (storage)

 

Applications

  • None Available

Aliases